4. Operation - PowerCommand 1.12-2016
51A045R242 (Issue 7) Copyright © 2016 Cummins Inc.
FIGURE 22. UTILITY POWERING BUILDING LOAD
9. The generator set runs for a 5-minute cooldown and shuts off.
FIGURE 23. TIME REMAINING UNTIL STOP
10. Normal operation resumes.
Exercise Sequence
The exercise sequence when the programmed exercise time is realized (the
generator set is in Auto Mode) is as follows:
1. The generator set starts and runs.
2. The Exerciser Scheduler On screen displays every 3 seconds and toggles
between the existing Information screen that is displayed for 1 second.
FIGURE 24. EXERCISER SCHEDULER SCREEN AND INFORMATION SCREEN
TOGGLE - EXAMPLE
3. The transfer switch is not commanded to switch the building load to the
generator set.
NOTICE
The user may navigate to other screens from the Information screens
during this duration. No functional keys are active on the Exerciser
Scheduler On screen.