Product Manual

Table Of Contents
4. Operation - PowerCommand 1.1 2-2016
52 A045R242 (Issue 7)Copyright © 2016 Cummins Inc.
4. The generator set stops after programmed exercise run time.
Manually Starting the Generator Set Sequence
If the generator set is manually started with the standard operator panel, HMI211
(the generator set is in Man Mode), the sequence is as follows:
NOTICE
Open the generator set main line circuit breaker to prevent the transfer
switch from transferring building load to the generator set.
1. In normal operation, the utility power is running to the transfer switch and then
to the building load, and the generator set is off.
2. Manually start the generator set via the standard control (HMI211) mounted on
the generator set.
FIGURE 25. MANUAL START SCREEN, STANDARD OPERATOR PANEL
3. The generator set starts and provides voltage to the transfer switch.
4. The generator set provides a signal to the transfer switch to transfer the
building load to the generator set.