4. Operation - PowerCommand 1.1 2-2016
54 A045R242 (Issue 7)Copyright © 2016 Cummins Inc.
Remote Starting the Generator Set Sequence
If the generator set is remote started with the in-home operator panel accessory, if
equipped (the generator set is in Auto Mode), the sequence is as follows:
1. In a normal operation, the utility power is running to the transfer switch and then
to the building load, and the generator set is off.
2. The generator set-mounted control (HMI211) is set in Auto Mode.
FIGURE 30. HMI211 SET IN AUTO MODE
3. Manually start the generator set via the in-home operator panel.