Spec Sheet

©2015 Cummins Inc. | NAS-5778d-EN (4/15)
power.cummins.com
Specification sheet
Quiet Connect
TM
Series
RS40
Features and benefits
Robust product design and testing - The
generator is designed to operate under extreme
environmental conditions including cold weather
starts at as low as -40
o
F. The generator is tested
and certified per the latest EPA, UL and IBC
Seismic standards and is capable of meeting
NFPA110 requirements when equipped with the
necessary accessories and properly installed.
Flexible Exercise mode - The innovative, flexible
exercise mode enables the generator to exercise
at a time, frequency and duration that suits the
customer's preference - as little as 2 minutes
every 6 months - reducing unnecessary fuel
consumption, emissions and noise.
Advanced Enclosure Design - The aesthetically
appealing enclosure incorporates special designs
that deliver the quietest generator of its kind.
Aluminum material plus durable powder coat
paint provides the best anti-corrosion
performance. The generator set enclosure has
been evaluated to withstand 180 MPH wind loads
in accordance with ASCE7-10. The intelligent
design has removable panels and service doors
to provide easy access for service and
maintenance.
Self diagnostics and easy service - The
generator is equipped with Cummins
PowerCommand electronic control to provide
industry-leading self diagnostic capabilities. In
addition, critical components of the generator are
designed to ensure service and preventive
maintenance can be completed in a short period
of time.
Weight, size and sound level
Weight:
1356 lbs (615 kg)
Size:
Length 94 in (2388 mm), width 34 in (864 mm), height 45.5 in (1156 mm)
Sound: 63 dB(A) at 23 ft (7 m) with sound level 2 enclosure
Series Model Phase Voltage (V) Frequency (Hz)
Rated amps
1
(NG/LPV fuel)
Circuit breaker
(Amps)
RS40 C40 N6
1 120/240 60 166.7/166.7 200
3 120/208 60 138.8/138.8 175
3 120/240 60 120.4/120.4 150
3 277/480 60 60.2/60.2 80
¹ Derating guidelines: Engine power available up to 114m (375 ft) at ambient temperatures up to 40 °C (104 °F). Above these elevations derate
at 4% per 305m (1000 ft) and 2% per 10 °C above 40 °C (104 °F).

Summary of content (6 pages)