Install Manual

2. Introduction3-2016
11A051X873 (Issue 5) Copyright © 2016 Cummins Inc.
2.4 Model Specifications
NOTICE
Damage caused by failure to follow the manufacturer's recommendation will
not be covered by the warranty. Please contact your authorized distributor.
TABLE 1. 5.9L MODEL VARIATIONS
Models Description
C45 N6, C50 N6, C60 N6, C70 N6, C80 N6, C100 N6 60 Hz, 1800 RPM
TABLE 2. COLD WEATHER SPECIFICATIONS (ALL MODELS)
Temperature Description
Battery
Type
Group
Above 40 °F (4 °C) Battery charger Standard 34
0 to 40 ° F (-17 to 4 °C)
Battery charger, coolant heater (1000W),
CCV heater
1
Standard 34
Below 0 °F (-17 °C)
Battery charger, coolant heater (1500W),
oil heater, battery heater, CCV heater
1
,
cold weather starter
2
Larger 4D
1
CCV heaters are provided as part of the cold and extreme cold coolant heater packages.
2
The cold weather starter is provided as part of the extreme cold coolant heater package.
NOTICE
For NFPA 110 applications, a coolant heater is required. A factory option is
available.
TABLE 3. FUEL SPECIFICATIONS 60 HZ, 1800 RPM
Type Unit C45 N6 C50 N6 C60 N6 C70 N6 C80 N6 C100 N6
Liquid
Propane
Full Load
scfh 289.6 321.6 370.2 384.2 420.8 518.7
BTU/hr 651,600 723,600 832,950 864,450 946,800 1,167,075
Natural
Gas
Full Load
scfh 711.2 806.3 933.8 988.4 1,083.5 1,317.7
BTU/hr 721,868 818,395 947,807 1,003,226 1,099,753 1,337,466