TABLE 7. GENERATOR SPECIFICATIONS 60 HZ, 1800 RPM
Type C45 N6 C50 N6 C60 N6 C70 N6 C80 N6 C100 N6
Generator Brushless, 4-pole rotating field, single bearing
Power (kVA) 1 Phase 45 50 60 70 80 100
Power (kVA) 3 Phase 56.3 62.5 75 87.5 100 125
Rated Voltages (V)
120/240, 1 Ph
227/480, 3 Ph
347/600, 3 Ph
120/240, 3 Ph
120/208, 3 Ph
127/220, 3 Ph
F1PO (Reconnectable, Full Single Phase Output)
NOTICE
Maximum I
2
= 8%. Generator set load unbalance must not exceed 25%
between any phases.
TABLE 8. GENERATOR SET DERATING GUIDELINES
Model Phase
Engine Power Available Up To... Derate At…
Elevation
Ambient
Temperature
Elevation Temperature
C45 N6 Both 2200 ft (675 m) 104 °F (40 °C)
4%
per 985 ft
(300 m)
2%
per 18 °F
(10 °C)
C50 N6 Both 490 ft (150 m) 77 °F (25 °C)
C60 N6 Both 3280 ft (1000 m)
104 °F (40 °C)
C70 N6
1 8450 ft (2575 m)
3 10000 ft (3048 m)
C80 N6
1 5985 ft (1825 m)
3 8200 ft (2500 m)
C100 N6
1 1560 ft (700 m) 77 °F (25 °C)
3 3280 ft (1000 m) 104 °F (40 °C)