2. Introduction3-2016
15A051X873 (Issue 5) Copyright © 2016 Cummins Inc.
TABLE 9. CONTROL SPECIFICATIONS (ALL MODELS)
Control Purpose
PC 1.1 Generator Set
Enovations I28 EPR Engine (45, 50, 60 kW Generator Sets)
Enovations 4G LDI Engine (70, 80, 100 kW Generator Sets)
TABLE 10. DC SYSTEM SPECIFICATIONS (ALL MODELS)
Type Specification
Nominal Battery Voltage 12 VDC
Battery Group
34 Standard, 4D High Capacity (Requires Large
Battery Tray)
Battery Type Maintenance-Free
Minimum Cold Crank Amps
850 Standard, 1080 High Capacity (Requires Large
Battery Tray)
TABLE 11. LUBRICATING OIL SYSTEM SPECIFICATIONS
Type Specification
Lubricating Oil Pressure at Idle (Minimum) 15 psi (104 kPa)
Lubricating Oil Pressure at Rated Speed (Minimum)
Filter Bypass Valve-Opening Pressure 45 psi (311 kPa)
Pressure Regulator Valve-Opening Pressure 65 psi (449 kPa)
Lubricating Oil Capacity (Standard Sump):
--High 15 qt (14.2 liters)
--Low 13 qt (12.4 liters)
--Total System 16 qt (15.1 liters)