Install Manual
Table Of Contents
- Table of Contents
- 1. Important Safety Instructions
- 1.1 Warning, Caution, and Note Styles Used in This Manual
- 1.2 General Information
- 1.3 General Precautions
- 1.4 Generator Set Voltage Is Deadly
- 1.5 Engine Exhaust Is Deadly
- 1.6 Fuel and Fumes Are Flammable
- 1.7 Batteries Can Explode
- 1.8 Vented Batteries
- 1.9 Moving Parts Can Cause Severe Personal Injury or Death
- 1.10 The Hazards of Carbon Monoxide
- 2. Introduction
- 3. Pre-Installation Considerations
- 4. Installation
- 5. Startup and Configuration
- Appendix A. Fuel Line Selection
- Appendix B. Outline and System Drawings
- Appendix C. Wiring Diagrams
- Appendix D. Seismic Requirements
4. Installation 3-2016
24 A051X873 (Issue 5)Copyright © 2016 Cummins Inc.
No. Description No. Description
1 Pad Length (Must Extend Minimum 6
in Beyond Skid)
6 Circuit Breaker 3 Stub-Up (Optional)
2 Pad Width (Must Extend Minimum 6 in
Beyond Skid)
7 5 ft Clearance (Shaded Area)
3 Pad Thickness (Minimum 5 in) 8 Accessory 120 VAC, 20A Max Wire
Stub-Up
4 Circuit Breaker 1 Stub-Up 9 Generator Set Control Wire Stub-Up
(DC)
5 Circuit Breaker 2 Stub-Up (Optional)
FIGURE 3. CONCRETE PAD PREPARATION
Lifting and Moving the Generator Set
WARNING
Heavy Load
The generator set is heavy. Handle with care.
Use appropriate lifting techniques to move the generator set. Do not use the
lifting eyes on the engine and alternator to lift the entire generator set.
Dropping the generator set can cause severe personal injury or death. Keep
feet and hands clear when lifting the generator set.










