Install Manual

5. Startup and Configuration3-2016
59A051X873 (Issue 5) Copyright © 2016 Cummins Inc.
5.5 Installation Checklist
Tick Item
General
Generator set wattage capacity is sufficient to handle maximum anticipated load.
At least 5 feet of clearance to combustible materials is provided. At least 3 feet of
clearance is provided around the entire generator set for service and ventilation.
The generator set is located in an area not subject to flooding.
All installers have read and are familiar with the Generator Set Installation manual and
the Health and Safety manual.
All installers have been thoroughly briefed on preventive maintenance procedures.
All installers have read and understand all important safety instructions.
Generator Set Support
The floor, roof or earth on which the generator set rests is strong enough and will not
allow shifting or movement. Local codes for soil bearing capacity were followed.
The generator set is properly supported and secured to an approved base.
The supporting base is of non-combustible material and extends 6 inches all around
the generator set.
Natural Gas and LP Vapor Fuel System
Fuel line size has been verified for generator set fuel consumption and pressure.
Approved flexible fuel line is installed between main fuel supply and the generator
set’s fuel system near the generator set
Fuel lines are properly installed, supported and protected against damage.
Fuel supply shutoff valves are installed to turn off fuel flow in case of leaks.
No leaks are found in fuel supply line as a result of leak testing fuel systems.
The inside of all fuel supply lines is free of contaminants.
Fuel pressure is at 6 - 12 inch water column (1.5 - 3.0 kPa).
Maximum pressure under any condition: 13 inch water column (3.2 kPa).
Fuel pressure maintains at least 6 inches water column (1.5 kPa) when the generator
set is at rated load.
The installation is compliant with all state and local codes and regulations.
AC and DC Wiring
The control is configured for the proper fuel type.
Wire sizes, wire types, insulation, conduits and connection methods all meet
applicable codes.