5. Startup and Configuration3-2016
61A051X873 (Issue 5) Copyright © 2016 Cummins Inc.
NOTICE
Before leaving the site, if the generator set is ready to be placed in service,
set the control switch to the AUTO position to provide automatic standby
power.
NOTICE
Contact your local Cummins service representative if you encounter a fault
code.
5.7 InPower Service Tool
The InPower
TM
service tool can be used in troubleshooting to perform tests, verify
control inputs and outputs, and test protective functions. Refer to the InPower
User's Guide, provided with the InPower software for test procedures.
5.8 Disabling the AMF Feature
NOTICE
This procedure must be performed by a qualified technician.
On single-phase units, the control is shipped with the Automatic Mains Failure
(AMF) feature enabled. This feature has logic to control the RA Automatic Transfer
Switch (ATS), including a 5-minute retransfer to utility delay. If you are not using an
RA ATS, you can eliminate the 5-minute retransfer to utility delay by disabling the
AMF feature using the instructions below.
NOTICE
This procedure is optional. If you do not disable the AMF feature, the
generator set will just run for an additional 5 minutes after the utility has
been restored.
NOTICE
These steps cannot be performed with the HMI211; they can only be
performed with the InPower service tool.
1. Connect to the PCC1302 via InPower.
2. Navigate to the Adjustments- >Features->Automatic Transfer Switch folder.
3. Select the Auto Mains Failure Enable parameter.
4. Double-click on Enabled in the Value field.
5. A pop-up will appear with available choices. Select Disabled.
6. Select Device->Save Adjustments from the top menu bar.