Product Manual

Table Of Contents
2. Introduction 9-2015
TABLE 7. GENERATOR SPECIFICATIONS 60 HZ, 1800 RPM
Type C45 N6 C50 N6 C60 N6 C70 N6 C80 N6 C100 N6
Generator Brushless, 4-pole rotating field, single bearing
Power (kVA) 1 Phase 45 50 60 70 80 100
Power (kVA) 3 Phase 56.3 62.5 75 87.5 100 125
120/240, 1 Ph
227/480, 3 Ph
347/600, 3 Ph
Rated Voltages (V) 120/240, 3 Ph
120/208, 3 Ph
127/220, 3 Ph
F1PO (Reconnectable, Full Single Phase Output)
NOTICE
Maximum I
2
= 8%. Generator set load unbalance must not exceed 25%
between any phases.
TABLE 8. GENERATOR SET DERATING GUIDELINES
Engine Power Available Up To... Derate At…
Model Phase
Ambient
Elevation Elevation Temperature
Temperature
C45 N6 Both 2200 ft (675 m) 104 °F (40 °C)
C50 N6 Both 490 ft (150 m) 77 °F (25 ° C)
C60 N6 Both 3280 ft (1000 m)
1 8450 ft (2575 m)
4% 2%
C70 N6
3 10000 ft (3048 m) 104 °F (40 °C) per 985 ft per 18 °F
(300 m) (10 °C)
1 5985 ft (1825 m)
C80 N6
3 8200 ft (2500 m)
1 1560 ft (700 m) 77 °F (25 °C)
C100 N6
3 3280 ft (1000 m) 104 °F (40 °C)
18 A051X877 (Issue 3)