Product Manual
Table Of Contents
- Table of Contents
- 1. Important Safety Instructions
- 1.1 Warning, Caution, and Note Styles Used in This Manual
- 1.2 General Information
- 1.3 Generator Set Safety Code
- 1.4 Batteries Can Explode
- 1.5 Moving Parts Can Cause Severe Personal Injury or Death
- 1.6 Electrical Shocks and Arc Flashes Can Cause Severe Personal Injury or Death
- 1.7 Fuel and Fumes Are Flammable
- 1.8 Exhaust Gases Are Deadly
- 1.9 The Hazards of Carbon Monoxide
- 1.10 Earth Ground Connection
- 2. Introduction
- 3. Manufacturing Facilities
- 4. Control System
- 5. Operation - PowerCommand 1.1
- 6. Maintenance
- 7. Troubleshooting
- 7.2 Engine Is Difficult to Start or Does Not Start
- 7.3 Code 143 - Engine Oil Pressure Low (Warning)
- 7.4 Code 151 - Engine Coolant Temperature High (Shutdown)
- 7.5 Code 155 - Intake Manifold Temperature High (Shutdown)
- 7.6 Code 197 - Coolant Level Low (Warning)
- 7.7 Code 415 - Engine Oil Pressure Low (Shutdown)
- 7.8 Code 441 - Battery Voltage Low (Warning)
- 7.9 Code 488 - Intake Manifold Temperature High (Warning)
- 7.10 Code 1438 - Fail to Crank (Shutdown)
- 7.11 Code 1472 - High AC Current (Shutdown)
- 7.12 Code 5134 - Unknown Shutdown at Idle
9-2015 5. Operation - PowerCommand 1.1
2. If the ambient temperature is below 20 °F (6.7 °C), the generator set will
idle at 800 rpm for up to 2 minutes to allow sufficient turbo lubrication.
• Idle time is linear from 2 minutes at -40 F (4 °C), or below to off at 20
°F (6.7 °C) or above.
FIGURE 25. COLD START IDLE ACTIVE
3. The Exerciser Scheduler On screen displays every 3 seconds and toggles
between the existing Information screen that is displayed for 1 second.
FIGURE 26. EXERCISER SCHEDULER SCREEN AND INFORMATION SCREEN
TOGGLE - EXAMPLE
4. The transfer switch is not commanded to switch the building load to the
generator set.
NOTICE
The user may navigate to other screens from the Information
screens during this duration. No functional keys are active on the
Exerciser Scheduler On screen.
5. The generator set stops after programmed exercise run time.
Manually Starting the Generator Set Sequence
If the generator set is manually started with the standard operator panel,
HMI211 (the generator set is in Man Mode), the sequence is as follows:
A051X877 (Issue 3) 55