Product Manual
Table Of Contents
- Table of Contents
- 1. Important Safety Instructions
- 1.1 Warning, Caution, and Note Styles Used in This Manual
- 1.2 General Information
- 1.3 Generator Set Safety Code
- 1.4 Batteries Can Explode
- 1.5 Moving Parts Can Cause Severe Personal Injury or Death
- 1.6 Electrical Shocks and Arc Flashes Can Cause Severe Personal Injury or Death
- 1.7 Fuel and Fumes Are Flammable
- 1.8 Exhaust Gases Are Deadly
- 1.9 The Hazards of Carbon Monoxide
- 1.10 Earth Ground Connection
- 2. Introduction
- 3. Manufacturing Facilities
- 4. Control System
- 5. Operation - PowerCommand 1.1
- 6. Maintenance
- 7. Troubleshooting
- 7.2 Engine Is Difficult to Start or Does Not Start
- 7.3 Code 143 - Engine Oil Pressure Low (Warning)
- 7.4 Code 151 - Engine Coolant Temperature High (Shutdown)
- 7.5 Code 155 - Intake Manifold Temperature High (Shutdown)
- 7.6 Code 197 - Coolant Level Low (Warning)
- 7.7 Code 415 - Engine Oil Pressure Low (Shutdown)
- 7.8 Code 441 - Battery Voltage Low (Warning)
- 7.9 Code 488 - Intake Manifold Temperature High (Warning)
- 7.10 Code 1438 - Fail to Crank (Shutdown)
- 7.11 Code 1472 - High AC Current (Shutdown)
- 7.12 Code 5134 - Unknown Shutdown at Idle
5. Operation - PowerCommand 1.1 9-2015
FIGURE 32. BUILDING LOAD TRANSFER IN PROCESS
6. If the ambient temperature is below 20 °F (6.7 °C) , the generator set will
idle at 800 rpm for up to 2 minutes to allow sufficient turbo lubrication.
• Idle time is linear from 2 minutes at -40 F (4 °C), or below to off at 20
°F (6.7 °C) or above.
FIGURE 33. COLD START IDLE ACTIVE
7. The transfer switch switches the generator set power to the building load.
The building is now running on generator power.
FIGURE 34. GENERATOR SET POWERING BUILDING LOAD
8. When the remote display Stop button is pressed, the transfer switch
switches back to utility power after a 5 minute retransfer delay.
FIGURE 35. BUILDING LOAD TRANSFER IN PROCESS
60 A051X877 (Issue 3)