Product Manual

Table Of Contents
9-2015 2. Introduction
Type Specification
Must adhere to Cummins
®
Engineering Standard
(CES) 20074
Use of improper oils can result in engine damage. Use
only the required oils:
5W-40 (all ambient temperatures)
15W-40 (above 40 °F [4 °C] ambient temperature)
(use of GEO 15W-40 oil in ambient temperatures
Oil Standards
below 40 °F [4 °C] could result in engine
turbocharger damage)
A sulfated ash limit of 0.6% mass has been placed on
all engine lubricating oils recommended for use in
Cummins® B, natural gas engines. Higher ash oils can
cause valve and/or piston damage, cause spark plug
fouling, and lead to excessive oil consumption and
degradation of the catalyst.
TABLE 5. GENERATOR SET SIZE SPECIFICATIONS
Enclosure
Size (L x W x H)
Type
98 x 40 x 58 in (2489 x 1016 x 1473 mm); does not include exhaust
Open/Weather
discharge elbow
Sound Level 1 119 x 40 x 58 in (3023 x 1016 x 1473 mm)
Sound Level 2 136 x 40 x 58 in (3454 x 1016 x 1473 mm)
TABLE 6. GENERATOR SET WET WEIGHT (POUNDS) (60 HZ, 1800 RPM)
Configuration C45 N6 C50 N6 C60 N6 C70 N6 C80 N6 C100 N6
Open 2180 2180 2431 2449 2587 2719
Weather 2359 2359 2610 2628 2766 2898
Sound Level 1 2455 2455 2706 2724 2862 2994
Sound Level 2 2485 2485 2736 2754 2892 3024
NOTICE
Weights are approximate and can be affected by selected options. Refer to
outline drawings for specific weight information.
A051X877 (Issue 3) 17