Features and Benefits
Robust product design and testing - The
generator is designed to operate under
extreme
environmental conditions including
cold weather
starts at as low as -40° F. The
generator is tested
and certified per the latest
EPA, UL and IBC
Seismic standards and is
capable of meeting
NFPA110 requirements
when equipped with the
necessary
accessories and properly installed.
Flexible exercise mode - The innovative,
flexible exercise mode enables the generator
to exercise at a time, frequency and duration
that suits the customer's preference - as little
as 2 minutes every 6 months - reducing
unnecessary fuel consumption, emissions
and noise.
Advanced enclosure design - The
aesthetically
appealing enclosure
incorporates special designs
that deliver
the quietest generator of its kind. Aluminum
material plus durable powder coat paint
provides the best anti-corrosion
performance. The
generator set enclosure
has been evaluated to
withstand 180 MPH
wind loads in accordance with
ASCE7-10.
The design has hinged doors to
provide
easy access for service and maintenance
Self-diagnostics and easy service - The
generator is equipped with Cummins
PowerCommand® electronic control to
provide
industry-leading self-diagnostic
capabilities. In
addition, critical components
of the generator are
designed to ensure
service and preventive
maintenance can be
completed in a short period of
time.
Weight, Size and Sound Level
Weight:
3915 lbs. (1776 kgs)
2
Size:
Length 143.0 in (3621 mm), width 40.0 in (1016 mm), height 72.0 in (1836 mm)
Sound: 71.3 dB(A) at 23 ft. (7 m) with sound level 2 enclosure
Series Model Phase Voltage (V)
Frequency
(Hz)
Rated amp
1
(NG / LPV)
Circuit Breaker
(Amps)
RS150 C150N6
1 120 / 240 60 625 / 625 600
3 120 / 208 60 520.3 / 520.3 600
3 277 / 480 60 225.3 / 225.3 250
3 120 / 240 60 450.9 / 450.9 600
1
Derating guidelines: Engine power available up to 775 m (2540 ft.) and ambient temperatures up to 40° C (104° F).
Above these conditions, derate at 4.25% per 300 m (985 ft.) and 2% per 10° C (18° F).
2
Weight above is average. Actual weight varies with product configuration