Product Manual

3. Installation 3-2016
22 A046S594 (Issue 12)Copyright © 2016 Cummins Inc.
Choose a vibration-free mounting surface that supports the weight of the switch. Avoid locations that are
near flammable liquids or gases, or are hot, moist, or dusty.
WARNING
An electrical arc occurs during transfer that can ignite a flammable atmosphere, resulting in
severe personal injury or death. The switch must not be located near batteries, fuel tanks,
solvents, or other sources of flammable liquids or gases, or in areas sharing ventilation with
such sources.
3.1.4 Installing Transfer Switches in Applications that Include a
Utility Panel
No. Description No. Description
1 Utility Source 5 Circuit Breaker
2 Utility Panel 6 Generator Source
3 Loads 7 Loads
4 Transfer Switch 8 Distribution Panel
FIGURE 14. PARTIAL COVERAGE SYSTEM (NON-SERVICE ENTRANCE MODEL)
NOTICE
Service entrance (SE) model transfer switches are rated service entrance equipment. The main
bonding jumper is factory installed in the connected position between Neutral and the Ground
bus bar. By installing a transfer switch as shown in the figure below, the main bonding jumper
should be removed or moved from a connected position to a disconnected position