4.2.2 Generator-to-Utility Sequence of Events
The following steps describe what normally happens when the transfer switch is connected to the
generator, utility power returns, and the switch moves from the Generator position to the Utility position.
1. The utility returns.
2. The generator control receives a ground (B-) signal from the TB4-1 utility sense relay.
3. The generator control de-energizes the relay coil (K1), which closes K1-1/K1-9 and K1-2/K1-10 and
opens K1-7/K1-11 and K1-8/K1-12 to move the transfer switch from the Generator position to the
Utility position.
4. The S1 auxiliary switch within the transfer switch mechanism breaks the signal to the ATS operator
coil (C).
5. The BSW limit switch removes the ground (B-) signal (TB4-6), signaling the transfer switch has
disconnected from the generator.
6. The ASW limit switch provides a ground (B-) signal to TB4-5, signaling that the transfer switch has
connected to the utility.
7. The load is retransferred to the utility.
8. After a delay to let the engine cool down, the generator stops.
4.2.3 Troubleshooting with Symptoms
Use the troubleshooting guide to help diagnose transfer switch problems. It is divided into sections based
on the symptom. Common problems are listed with their possible causes. Refer to the corrective action
column for the appropriate test or adjustment procedure. The section in the right column lists the location
of the test or adjustment procedure in the manual.
Always refer to the schematic and wiring diagram package that was shipped with the transfer switch for
specific information about its configuration.
Make a thorough inspection of the transfer switch wiring to make sure that good wire harness and ground
connections are made. Correct wiring problems before performing any test or replacing any components.
4.2.4 Important Troubleshooting Reminders
When troubleshooting the transfer switch, it is important to remember the following:
The generator control may use limit switches (ASW and BSW) on either side of the transfer switch to
determine if the switch has opened or closed. If either the ASW or BSW limit switches are bad, the
generator control may display a transfer switch signal failure.
This is a two position transfer switch. It can be connected only to either one source. There is no
neutral position.
The generator control energizes relay coil K1 by supplying B+ (CH13N6H, CH17N6H, CH20N6H) or
a B- (all other models).
Terminal Block Jumper (A034N106) provided with Generator Set is installed between TB4-3 and TB-
4 on Air Cooled Generator Sets (CH13N6H, CH17N6H, CH20N6H).
The transfer switch design is intended to signal when the utility voltage is not present and when it returns.
The utility sense relay coil will energize or stay energized at voltages other than nominal. Therefore, the
unit should not be expected to signal a failed utility to the genset during utility undervoltage or overvoltage
conditions.