Product Manual

5. Transfer Switch Service 3-2016
56 A046S594 (Issue 12)Copyright © 2016 Cummins Inc.
No. Description No. Description
1 Relay 3 Base
2 Clip
FIGURE 29. CONTROL RELAY INSTALLATION
5.6 Circuit Breaker Replacement Procedures
These procedures are only for RA Series service entrance transfer switches.
WARNING
The transfer switch presents a shock hazard that can cause severe personal injury or death.
Before beginning installation, remove all sources of AC power. If a generator provides
emergency power, move the generator operation selector switch to Stop, disconnect AC line
power, disconnect the battery charger from its AC power source, and disconnect the starting
battery (negative [-] lead first).
1. RA 100A/200A transfer switch models only:
a. Remove all sources of power from the transfer switch in the following order.
i. Move the operation selector switch on the generator set to Stop (Off).
CAUTION
Always disconnect a battery charger from its AC source before disconnecting the
battery cables. Otherwise, disconnecting the cables can result in voltage spikes
high enough to damage the DC control circuits.
ii. If there is an external battery charger, disconnect the battery charger from its AC power
source.