5. Transfer Switch Service 3-2016
60 A046S594 (Issue 12)Copyright © 2016 Cummins Inc.
FIGURE 31. RA 400A CIRCUIT BREAKER
5.7 Utility Sense Relay (K2) Replacement Procedure
WARNING
The transfer switch presents a shock hazard that can cause severe personal injury or death.
Before beginning installation, remove all sources of AC power. If a generator set provides
emergency power, move the generator set operation selector switch to Stop, disconnect AC line
power, disconnect the battery charger from its AC power source, and disconnect the starting
battery (negative [-] lead first).
1. Remove all sources of power from the transfer switch in the following order.
a. Move the operation selector switch on the generator to Stop (Off).
CAUTION
Always disconnect a battery charger from its AC source before disconnecting the
battery cables. Otherwise, disconnecting the cables can result in voltage spikes high
enough to damage the DC control circuits.
b. If there is an external battery charger, disconnect the battery charger from its AC power source.
WARNING
Ignition of explosive battery gases can cause severe personal injury. Do not smoke or
cause any spark, arc, or flame while servicing batteries.