Product Manual

5. Transfer Switch Service3-2016
61A046S594 (Issue 12) Copyright © 2016 Cummins Inc.
WARNING
Accidental starting of the generator set can cause severe personal injury or death due
to electrocution or contact with moving parts. Disconnect the starting battery cables,
before performing service. Batteries emit hydrogen, a highly explosive gas.
Thoroughly ventilate the battery compartment before removing battery cables. Remove
the negative (-) cable (s) first to reduce the risk of arcing.
c. Disconnect the generator starting battery (negative [-] lead first).
WARNING
If the cabinet must be opened for any reason, remove AC power to the automatic
transfer switch. If the instructions require otherwise, use extreme caution due to the
danger of shock hazard.
d. Remove AC power to the automatic transfer switch.
2. Remove the transfer switch cabinet door panel.
3. Grasp the relay and pull it straight out of the socket (see Figure 20).
4. Place the new relay on the socket while aligning pins to socket holes.
5. Firmly push the relay straight down onto the socket until you feel the relay is seated securely.
6. Restore power.
a. Reconnect the generator starting battery (negative [-] lead first).
b. If there is an external battery charger, reconnect the battery charger to its AC power source.
c. Restore AC power to the automatic transfer switch.
d. Move the operation selector switch on the generator to the Remote (or Auto) position.