Installation Guide
2. Introduction 1-2014
TABLE 2. COLD WEATHER SPECIFICATIONS TABLE
60 Hz 50 Hz
Propane Vapor Natural Gas Propane Vapor Natural Gas
Operating Temperature Range
Above 32 °F (0 °C) and low No dryers or starting aids required.
humidity
High humidity Alternator drying heater recommended.
Below 20 °F (-7 °C) Additional oil heater recommended for starting. Factory-installed model available.
Below 0 °F (-18 °C) Additional accessory breather shield/shroud required to avoid possible engine
damage. See warranty statement.
Below -10 °F (-23 °C) Additional accessory battery blanket recommended for starting.
Below -20 °F (-29 °C) Not warranted. See warranty statement.
TABLE 3. GENERATOR SET SPECIFICATIONS TABLE
60 Hz 50 Hz
Propane Vapor Natural Gas Propane Vapor Natural Gas
Dimensions
Weight (With Oil) 540 lbs (245 kg)
Size (L x W x H) 48 x 43 x 34.6 in (1219 x 864 x 880 mm)
Noise 62 dB(A) at 23 ft (7 m) at normal load. (Normal load is equal to the typical
household consumption of 3 KW.)
TABLE 4. FUEL SPECIFICATIONS TABLE (SPEC A AND CANADIAN GSBB SPEC B)
60 Hz 50 Hz
Propane Vapor Natural Gas Propane Vapor Natural Gas
Fueling
1/2 Load 132,500 Btu/Hr 135,000 Btu/Hr 122,000 Btu/Hr 114,000 Btu/Hr
53 ft
3
/Hr 135 ft
3
/Hr 48 ft
3
/Hr 111 ft
3
/Hr
Full Load 275,000 Btu/Hr 240,000 Btu/Hr 229,000 Btu/Hr 213,000 Btu/Hr
109 ft
3
/Hr 233 ft
3
/Hr 91 ft
3
/Hr 207 ft
3
/Hr
Fuel Pressure (all loads)
7-11 inches WC 5-11 inches WC 7-11 inches WC 5-11 inches WC
As measured at genset fuel
regulator service port
Tank Size Contact your local gas company to verify the tank size required for your application.
6 A029V088 (Issue 16)