Installation Guide
1-2014 3. Step-By-Step Outline of Installation
FIGURE 7. OPERATOR PANEL BEZEL
3.7.6 Load Shed Communications Wires
The control cable has the load control wires brought out of the genset (P7-7 and P7-8). Class 1
wiring methods should be used for the in-home display, Ethernet and transfer switch
communication conductors between the generator set and transfer switch. Separation of Class 2
and power circuits should be maintained per Article 725.136 of 2008 NFPA 70: National
Electrical Code.
Use 300V 18 gauge 75 °C wire for wiring the relay.
See the following figures for the different ways the relays can be wired.
A029V088 (Issue 16) 23