Installation Guide
3. Step-By-Step Outline of Installation 1-2014
3.8.4.1 Recommended Fuel (Propane)
WARNING
Propane presents the hazard of fire or explosion that can cause severe personal injury
or death. Do not permit any flame, spark, arc-producing equipment, switch, pilot light,
cigarette or other ignition source near the fuel system. Keep an ABC type fire
extinguisher nearby.
Use clean, fresh HD-5 grade Propane or equivalent product consisting of at least 90% Propane.
NOTICE
Commercial Propane may contain more than 2.5% butane, which can result in poor fuel
vaporization and low tank pressure - resulting in poor engine staring in below 32 °F (O
°C) temperatures.
3.8.4.2 Propane Tank Size
First, some Propane tank facts to bear in mind when figuring the proper Propane tank size:
• Propane tanks are sized by the number of gallons of water they can hold, not the amount
of fuel they can hold.
• Propane tanks are generally filled to only 80% of their water capacity. Therefore, a 500 lb.
tank results in 400 lb. tank capacity.
• Low ambient temperatures affect the amount of fuel available from the Propane tank.
• Approximately 60% of the fuel (in gallons) filled in the tank can be effectively used.
Therefore, a 500 lb. tank results in 300 gallon capacity.
To assist in the proper selection of the Propane tank, follow the guidelines below.
• Propane tanks must be fitted with a pressure reducing regulator before connection to the
generator set to prevent fuel system damage.
• Propane tanks must be located at least 10 ft. (3048 mm) from any source of combustion
(including the generator set).
TABLE 17. REQUIRED PROPANE TANK SIZE IN GALLONS (LITERS) FOR INDICATED
TEMPERATURES WHEN KEPT AT LEAST HALF FULL
Withdrawal Lowest Average Winter Temperature
Rate
32 °F (0 °C) 20 °F (-7 °C) 10 °F (-12 0 °F (-18 °C) -10 ° F (-23 -20 °F (-29 -30°F (-34
°C) °C) °C) ° C)
100 cfg 250 250 250 400 500 1000 1500
(250,000
(945) (945) (945) (1515) (1890) (3785) (5675)
BUT/hr)
[2.8 m
3
/hr (264
MJ/hr)]
150 cfg 300 400 500 500 1000 1500 2500
(375,000
(1135) (1515) (1890) (1890) (3785) (5675) (9640)
BUT/hr)
[4.2
m
3
/hr(395.6
MJ/hr)]
32 A029V088 (Issue 16)