FIGURE 17. WELCH PLUG INSTALLATION (US GSBB SPEC B AND CANADIAN GSBC SPEC B
ONLY)
3.8.5 Testing the Fuel System for Leaks
WARNING
Fuel presents the hazard of explosion or fire which can result in severe personal injury
or death. Do not smoke or allow any flame, spark, pilot light, arc-producing equipment,
switch or other ignition sources around fuel or fuel components.
Before operating the generator set, test the fuel system for leaks.
• Energize the fuel solenoid from a separate 12-volt DC source before testing the fuel
system
NOTICE
Testing for gas leaks with a flame can cause a fire or explosion that can lead to severe
personal injury or death. Use approved methods only.
After assembly, and before initial operation, all fuel system connections, hose valves, regulators
and fittings must be tested and proven free of leaks using a soap-and-water (or equivalent)
solution while the system is under gas or air pressure of at least 1.5 times the supply pressure
or 3 psi (20.7 kPa) minimum.
• Apply the soap-and-water solution to all fuel system connections, hose valves, regulators
and fittings.
• When the system is running, bubbles will form where air/pressure is leaking from the
system.
Other approved methods of detecting leaks can be used if appropriate. DO NOT use a flame to
test for gas leaks.