Installation Guide
7. Startup and Configuration 1-2014
7.7.2 To Calibrate the Display Meter
Use the following procedure:
1. Connect an accurate AC volt meter across L1 and L2 while the generator set is running.
2. Press the NEXT button to select the Display Cal field (screen not shown).
3. Press the up or down arrow to adjust the voltage reading on the screen until it matches the
meter reading.
4. Press the BACK button to save the settings and return to the home screen.
FIGURE 61. ADJUSTMENT MENU SCREEN
82 A029V088 (Issue 16)