Use and Care Manual

3. Operation 1-2014
3.3.3 To Adjust the Output Voltage
Use the following procedure:
1. Connect an accurate AC volt meter across L1 and L2 while the generator set is running.
2. With Output Volts selected on the Adjustments Menu screen, press the up or down arrow
button to adjust the voltage to the desired setting
3. The control allows an adjustment of 240 VAC ± 7% (17 VAC).
4. Press the BACK button to save the settings and return to the home screen.
3.4 To Enable/Disable Standby
Normally, you should not have to disable generator set STANDBY.
STANDBY should always be enabled (ON) except during maintenance/service.
STANDBY will have to be re-enabled (STANDBY OFF light on) if the generator set is
started or stopped manually (normally a maintenance/service function) or a fault shutdown
has occurred.
CAUTION
When STANDBY is disabled the generator set will NOT automatically start to supply power if
utility power is interrupted.
To enable or disable generator set standby:
1. Press the STANDBY ON/OFF button on the operator panel, which takes you to the
Standby ON/OFF screen.
2. Press the up or down arrow button to select ON or OFF.
3. To enable STANDBY select ON and press the BACK button. The STANDBY OFF lamp
will go out and the display will state: “Standby ready enabled by user."
4. To disable STANDBY select OFF and press the BACK button. The STANDBY OFF lamp
will come on and the display will state: “Standby ready disabled by user."
FIGURE 10. ENABLE/DISABLE STANDBY SCREEN
18 A029V089 (Issue 9)