TABLE 4-2. TROUBLESHOOTING TRANSFER SWITCHES WITH AN OPERATOR PANEL (CONTINUED)
AC power within the cabinet presents a shock hazard that can cause severe personal
injury or death. Do not remove the front panel under any circumstances.
Improper operation of the generator presents a hazard that can cause severe personal
injury or death. Observe all safety precautions in your generator manuals.
WARNING
WARNING
Problem Corrective ActionPossible Cause
The generator did not exer-
cise when expected to.
1. The selector switch on generator
control panel may not be in the cor-
rect position.
2. An exercise period may not be set
or is set but not yet started.
3. There may be generator problems.
1. Verify that the operation selector
switch on the generator control pan-
el is set to the Remote position.
2. Check the Exercise LED on the con-
trol panel to see if it is lit.
a. If the Exercise LED is not lit, no
exercise period has been set.
Refer to the generator exerciser
section for information on setting
an exercise.
b. If the Exercise LED is lit but not
flashing, the exercise period has
not yet started. Exercisers do not
display exercise start and stop
times.
3. Try starting the generator using its
start-stop controls. If it does not
crank, check the starting batteries
and cable connections. If it cranks
but does not start, check the fuel
supply.
If the problem persists, contact your lo-
cal Cummins distributor for service.