Model kW Phase Amps Voltage (L-N/L-L) V
C125D6C 125
3 434 120/208
3 410 127/220
3 376 120/240
3 188 277/480
3 150 347/600
1 521 120/240
TABLE 2. COLD WEATHER SPECIFICATIONS (ALL MODELS)
Temperature Description Battery Type Group
Above 10 °C (50 °F) No starting aids required. Standard 34
-17 to 10 °C (0 to 50 °F)
All starting aids (battery heater,
1000 W coolant heater, battery
charger) recommended. Factory
options available.
2 Standard 34
Below -17 °C (0 °F)
All starting aids (battery heater,
1500 W coolant heater, battery
charger) recommended. Factory
options available.
2 Standard 34
NOTICE
For NFPA 110 applications, a coolant heater is required. A factory option is
available.
TABLE 3. FUEL SPECIFICATIONS (PER HOUR)
Full Load Rating C50D6C C60D6C C80D6C C100D6C C125D6C
Standby 50 227.1 L
(60 gal)
303 L
(80 gal)
379 L
(100 gal)
473.1 L
(125 gal)
Prime 45 204.4 L
(54 gal)
273 L
(72 gal)
341 L
(90 gal)
426 L
(112.5 gal)