Product Manual

3. Pre-Installation Considerations2-2017
21A055H194 (Issue 3) Copyright © 2017 Cummins Inc.
California Administrative Code - Title 25 Chapter 3 State of California
Documents Section
P.O. Box 1015
North Highlands, CA 95660
3.3 Required Items for Installation
Tools and materials are used for the installation of this generator set. These items
are identified in the following sections. Please refer to local codes and standards,
because they may affect the materials required.
Materials Required
NOTICE
Refer to local codes and standards, which may affect material requirements.
NOTICE
If a 100% rated breaker is used, 90 °C wire must be used for L1, L2, and L3
with the wire size determined by the 75 °C ampacity tables.
NOTICE
A UL-listed grounding electrode terminal within its ratings and suitable for
the application must be installed and labeled “Grounding Electrode
Terminal”.
Electrical Materials:
NOTICE
Class 1 wiring methods must be used for connecting the generator set.
Four code compliant AC power wires will be needed: L1, L2, N and Gnd (add
another wire for 3-phase for a total of 5 AC wires)
For RA switches, 4 DC control wires will be needed from the generator to the
transfer switch.
Wire sizes (DC control and power and AC sense only):
DC control or AC sense wires under 1000 feet circuit length => 18-14
AWG of the insulation type below