Product Manual
4. Installation2-2017
45A055H194 (Issue 3) Copyright © 2017 Cummins Inc.
Drilling Locations for Electrical Connections
Route the electrical leads vertically through conduit that is installed in the mounting
pad that terminates in the electrical connection areas. Refer to the Outline and
system Drawings appendix for the location of electrical connection areas. Comply
with NEC and local codes and standards for the installation of wires for electrical
circuits. Refer to NEC standards for required wire bend radius and ampacity of load
leads.
No. Description No. Description
1 Circuit Breaker 2 Maximum 3 in. Bend Radius Gap
FIGURE 13. CABLING ROOM FOR CIRCUIT BREAKER
Grounding
NOTICE
The generator set is shipped from the factory with the neutral and equipment
ground not bonded together.
Refer to local codes and standards for grounding procedures.
Battery
CAUTION
Ensure that the AC power to the battery charger is disconnected when
installing the battery.
CAUTION
Wear proper safety protection when working around batteries. Keep open
flames and sparks away from the equipment.