Product Manual

5. Startup and Configuration2-2017
65A055H194 (Issue 3) Copyright © 2017 Cummins Inc.
Check Description
Exhaust Outlet
Make sure: that exhaust components are secured and not warped; that
the exhaust outlet is unobstructed; that no combustible materials are
near the system; that gases are discharged away from building
openings; and that there are no leaks and that all fittings are tight.
Batteries
Make sure that the batteries are charged, and that all connections are
correct and tight.
Auxiliary AC
Supplies
Make sure that all auxiliary equipment is receiving power from the
customer’s supply.
Emergency Stop Make sure that the emergency stop button is fully operational.
Starting at the Operator Panel (Manual Run Mode)
NOTICE
Make sure that all Pre-start Checks are carried out before starting the
generator set. Do not attempt to start the generator set until it is safe to do
so. Warn all others in the vicinity of the generator set and connected load
equipment that the generator set is about to start.
STARTING IN MANUAL RUN MODE
1. Make sure the main circuit breaker is in the open position.
2. To start the generator set in the Manual Run mode:
a. Press the Manual button on the operator panel.
b. Press the Start button within ten seconds.
NOTICE
Failure to press the Start button within this time will result in the
generator set changing to the Off mode. Refer also to the Selecting
Manual Run Mode section.
NOTICE
If the mode change access code feature has been enabled, enter the
access code when prompted. See the Passwords and Mode Change
Access section.