Product Manual

©2015 Cummins Inc. | NAS-6254 (A056T581) (01/17)
power.cummins.com
Specification sheet
Quiet Connect
TM
Series - RS13A,
RS17A, RS20A, &
RS20AC
Features and benefits
Robust Design – The generator is designed
to operate in cold weather with performance
down to 0 °F (-18 °C) out of the box. Cold
Weather accessories allow for even colder. It
is tested and certified per the latest EPA, UL,
and CSA standards. The generator meets
NFPA 37 which allows it to be installed 18
inches from a building. It has powerful motor
starting ability and can easily start and run a 5
ton A/C¹ under full pre-load.
Flexible Exercise Modes - Exercise modes
can be set for time, date, and frequency that
suits the owner. Our patented ‘Crank only’
exercise mode allows the generator to crank
the engine and run diagnostics without
starting the engine. This reduces wear and
tear on the engine, fuel costs, and further
reduces the sound of an already quiet
generator.
Intelligent Load Management - The
generator can control up to 4 loads and
continuously monitors how much power is
required independently for each load. It then
controls each load for maximum utilization of
generator power by only restoring loads the
generator has capacity to run.
Remote Monitoring - Remote monitoring is
built into every generator. Using a computer,
tablet, or smart phone, an operator can
monitor, change exercise modes, and
manually run the generator remotely.
Generator and ATS packaged sets
– The
RS20AC comes with a 20 kW generator and
200A service entrance rated ATS in one box
to make ordering more convenient.
Weight, size and sound level
Size:
Length 34.1 in (865 mm), width 36.0 in (915 mm), height 27.3 in (694 mm)
Sound: 65 dB(A) at 23 ft. (7 m) at normal load
2
Series Model
Part
number
Voltage
(V)
Frequency
(Hz)
Rated amp
3
(NG / LPV)
Weight
Lbs. / Kg
RS13A
C13N6H A054E399 120 / 240 60 54.2 / 54.2 479 / 217
RS17A
C17N6H A054E397 120 / 240 60 70.8 / 70.8 540 / 245
RS20A
C20N6H A054E395 120 / 240 60 75 / 83.3 540 / 245
RS20AC
C20N6HC A054X497 120 / 240 60 75 / 83.3 540 / 245
¹
Air-conditioners vary by type, efficiency, operational conditions, etc. Consult with a qualified HVAC specialist or Cummins Power
Generation distributor/dealer for proper sizing.
²
Quietest point at a normal load. Sound performance may be affected by installation. Normal load is defined as typical household
consumption of 3kW.
³ Derating guidelines: Maximum wattage or maximum current are s
ubject to and limited by such factors as fuel Btu content, ambient
temperature, altitude, engine power and condition, etc. Full rated power available at the following:
RS20A & R20AC – at 15 °C (60 °F) and 0 m (0 ft.). Derate 3.5% for each increase of 300 m (1000 ft.) and 1% for each
increase of 5.5 °C (10 °F)
RS17A - at 25 °C (77 °F) and 300 m (1000 ft.). Derate 3.5% for each increase of 300 m (1000 ft.) and 1% for each
increase of 5.5 °C (10 °F)
RS13A – at 25 °C (77 °F) and 2100 m (6900 ft.). Derate 3.5% for each increase of 300 m (1000 ft.) and 1% for each
increase of 5.5 °C (10 °F)

Summary of content (5 pages)