Installation manual
Natural Gas Generator Set Installation Manual-GF Series
Doc. 17855, Rel. 03/2014
3-11
3.15 Remote Radiator Cooling Require-
ments (Available on All Models)
The remote radiator cooling system substitutes a
remote mounted radiator and an electrically driven
fan in place of mounted components. Removal of the
radiator and the fan from the set reduces noise levels
without forcing dependence on a continuous cooling
water supply (necessary with heat exchanger cool-
ing). The remote radiator installation must be com-
pletely protected against freezing.
Remote radiator plumbing will vary with installation.
Follow recommendations given in Cummins Applica-
tion Manual T-030. See product Data Sheet provided
with the genset (visit www.cumminsnpower.com for
genset specifications) for friction head and static
head limits.
IMPORTANT: Before filling cooling system, check all
hardware for security. This includes hose clamps,
capscrews, fittings and connections. Use flexible
coolant lines with heat exchanger or remote mounted
radiator options.
1. Thimble
2. 3-Way Catalyst
3. Exhaust Line
4. Silencer
5. Condensation Drain Plug
6. Sweeping Elbow
7. Flexible Sections
8. Control Wiring
9. Power Wiring
10. Air Inlet
11. Level Concrete Base
12. Seismic Isolators (Optional)
13. Flexible Bellows
14. Air Outlet
Figure 3-6 Generator Set Installation (Typical)
NG-00041
1
2
4
5
6
7
8
9
11
12
13
14
10
3