Installation manual

Natural Gas Generator Set Installation Manual-GF Series
Doc. 17855, Rel. 03/2014
4-3
Figure 4-1
Switched B+: (Fused at 5 amps.) Same as Relay
Connection description.
B+: (Fused at 10 amps.) Same as Relay Connection
description.
4.4 Control Relays (Optional)
CAUTION
Damage to the base board can occur if the
voltage suppressors are not installed across
relay coils (A1/A2) of control relays K11, K12 and
K13 before connecting genset battery cables.
The three optional control relays are rail mounted
inside the control panel housing. Each relay is a 4-
pole relay with 2 poles normally open and two poles
normally closed.
These relays are used to control auxiliary equipment,
such as fans, pumps and motorized air dampers.
Energizing of the relays is user definable.
The contacts are rated at 10 amps at 600 VAC.
Refer to Customer Connections diagram in Section 7
- Wiring Diagrams.
4.5 AC Electrical Connections
This section provides the procedure that is used to
connect the AC electrical system of the genset.
Before making any AC electrical connections, make
certain the generator set cannot be accidentally
started. Place the control panel run switch in the OFF
position. Turn off or remove AC power from the
battery charger, depress the E-Stop, and then
remove the negative (-) battery cable from the set
starting battery.
WARNING
Ignition of explosive battery gases can cause
severe personal injury or death. Arcing at battery
terminals, light switch or other equipment, flame,
pilot lights and sparks can ignite battery gas. Do
not smoke, or switch trouble light ON or OFF near
battery. Discharge static electricity from body
before touching batteries by first touching a
grounded metal surface.
Ventilate battery area before working on or near
battery—Wear goggles—E-Stop gen set and dis-
connect charger before disconnecting battery
NG-00052
NG-00052