Installation manual

Natural Gas Generator Set Installation Manual-GF Series
Doc. 17855, Rel. 03/2014
6-2
6.5 Exhaust System
Operators are thoroughly briefed on the dangers of carbon monoxide gas.
Areas around set are well ventilated. No possibility of exhaust fumes entering building doors, windows, or
intake fans.
Exhaust gases are piped safely outside and away from building.
The correct length of approved rigid pipe is connected to the generator set flexible pipe using approved
securing methods with no weight resting on engine exhaust components. There are no bends in flex section.
Condensation drain is provided in lowest section of exhaust piping.
Exhaust piping is insulated to guard against burns to personnel.
Exhaust piping passing through walls or ceilings have approved fire-proof materials and are in compliance
with all codes.
Exhaust piping is large enough in diameter to prevent excessive back pressure on engine.
For model GTA855E, verify O2 and temperature sensors are installed pre and post catalyst.
6.6 AC And DC Wiring
Wire sizes, insulation, conduits and connection methods all meet applicable codes.
AC and DC wires are separated in their own conduit to prevent electrical induction.
All load, line and generator connections are proper and correct.
Flexible conduit between generator set and building or surrounding structure.
6.7 Generator Set Pre-Start
Generator set engine is properly serviced with oil and coolant.
E-Stop is depressed.
Batteries are properly installed, serviced and charged.
Battery charger and engine coolant heater are connected and operational.
All generator set covers and safety shields are installed properly.