Service manual
9-2013 4. Service
No. Description
1 Fully closed actuator
2 Lever touches set screw
FIGURE 7. GOVERNOR ACTUATOR - CLOSED
4.5.4 Governor Linkage Adjustment (50 Hz LP Only)
NOTICE
It is beneficial to remove the air cleaner including the base for this procedure and to
place a clean rag in the "V" between the cylinders to catch any small fasteners that may
drop.
Due to inconsistencies in fuels, operating temperatures and engine variation, it may be
necessary to adjust the linkage in order to achieve the proper no load frequency (primarily in 50
Hertz LP applications).
1. Loosen the fasteners that hold the actuator.
2. Slide the actuator to its furthest point away from the butterfly.
3. Tighten both fasteners to 6 in-lb-f.
A030A239 (Issue 10) 27