Service manual

6. Startup and Configuration 9-2013
NOTICE
Before leaving the site, if the genset is ready to be placed in service, set the control switch to the
REMOTE position to provide automatic standby power.
6.3 Generator Set Configuration
The operator panel has a menu with four generator set/transfer switch parameters that must be
configured for the installation.
To configure the generator set:
1. Press the MENU button on the home screen.
2. Press and hold the blank (far left, solid black) button on the menu screen for at least 5
seconds to go to the Config Menu.
3. Press the up or down arrow button on the Config Menu screen to select Generator Config.
4. Press Enter on the Config Menu to go to the Generator Config screen.
5. Press the NEXT button on the Generator Config Menu screen to select the Config,
Frequency or Rating field.
6. Press the up or down arrow button to increase or decrease the configuration parameter.
a. Config: Select appropriate configuration (depending on model and fuel) from the table
shown below.
b. Frequency: Select 60 Hz or 50 Hz.
c. Rating: Rating will be filled in, based on the configuration selected. This value can be
lowered in order to correctly de-rate for high altitude or hot climates. (Selecting the
correct Amps value will also allow the correct genset load to be displayed on the
Operator Panel.
d. Press the BACK button to save the setting and return to the home screen.
TABLE 14. CONFIGURATIONS, BASED ON MODEL AND FUEL TYPE
Model (Spec) Fuel Configuration
GSBB Spec A and Canadian GSBB Natural Gas 14
Spec B
GSBB Spec A and Canadian GSBB Propane 15
Spec B
US GSBB Spec B and Canadian Natural Gas 18
GSBC Spec B
US GSBB Spec B and Canadian Propane 19
GSBC Spec B
60 A030A239 (Issue 10)