Specifications
18
CLEANING THE SPARK ARRESTOR
Refer to Table 3 for scheduled cleaning of the spark
arrestor muffler (which meets U.S. Forest Service
requirements). Cleaning is required for maximum
genset performance.
WARNING
A hot muffler can cause severe
burns. Let the muffler cool down before remov-
ing or installing the cleanout plug.
The muffler is mounted inside the genset housing.
The cleanout plug is located on the side of the muf-
fler, accessible through the air outlet opening in the
bottom of the genset. Clean out the spark arrestor
muffler as follows:
1. Remove the cleanout plug from the muffler
(Figure 8).
2. Restart the genset and load it nearly to full pow-
er. See LOADING THE GENSET (Page 9).
Let the genset run for about five minutes to ex-
pel the soot in the muffler.
3. Stop the genset, allow the muffler to cool down
and then reinstall the plug.
CLEANOUT PLUG
FIGURE 8. SPARK ARRESTOR CLEANOUT PLUG