Installation manual

4-2010 3. Step-By-Step Outline of Installation
Appropriately-sized junction box and cover for heater/GFCI wiring (if installing). X
Provided on cold weather model.
Code compliant GFCI outlet and "While in Use - Wet Location" cover. X
Cat 5e for Internet installation. X
Two conductor 300V wire (18AWG) per Load Management relay. X
Low Voltage: SPDT relay min 1A 24VAC. X
High Voltage: SPDT relay sized to load (amp and voltage). X
TABLE 11. MOUNTING MATERIALS
Required Optional
Four base mounting spikes. Provided with generator. X
Cummins Onan Installation Wheel Kit is available for easy on-site generator X
transportation.
TABLE 12. FUEL MATERIALS
Required Optional
12" Flexible fuel line. Provided with generator. X
UL Listed pipe thread sealant. X
Size Fuel line. NG: 5-11" H20, LP: 7-11" H20 fuel pressure. See Installation Manual X
guidelines.
Fuel regulator - as required.
Manual fuel shut-off at Genset (preferred). X
TABLE 13. IN-HOME DISPLAY MATERIALS
Required Optional
In-home display. One (1) provided with generator. X
Four wall anchors and screws (no. 6) if mounting on stud wall. X
Standoffs and mounting fasteners if mounting on block or brick wall. X
3.1.2.1.1 Loose Parts Shipped With the Generator
The following loose parts are shipped with the generator set:
· Oil drain hose
· Flexible fuel hose assembly
· Four base spikes (ground stakes)
· In-home display
· Two keys
· Literature - Operator Manual (A029V089), Installation Manual (A029V088) and Warranty
Statement
A029V088 (Issue 2) 11