Manual
Jumper Settings 
For Zone 1 to operate as a master zone the following steps must be adhered 
to: 
5 Zone Panel 
Step 1 
The following jumpers should be enabled for zone 1 to act as a master: 
J16, J18, J19 
Jumpers J20 – J24 configure zones 1-5 respectively to operate alongside 
zone one. 
E.g Jumper J23 will enable zones 2-4 to act in tandem with the master zone. 
Therefore zone 5 will remain operating independently. 
Step 2 
Remove Jumper J29 – Note there must be no trigger input at terminal J33 
(Link1). 
10 Zone Panel 
Step 1 
The following jumpers should be enabled for zone 1 to act as a master: 
Upper circuit board: J16, J18, J15 
Jumpers J20 – J24 configure zones 1-5 respectively to operate alongside 
zone one. If using more than 5 zones with the master insert a jumper on to 
J24 to continue the master on to the lower circuit board. 
Lower circuit board: J17 
Jumpers J20 – J24 configure zones 6-10 respectively to operate alongside 
zone one. 
E.g Jumper J23 will enable zones 2-9 to act in tandem with the master zone. 
Therefore zone 10 will remain operating independently. 
Step 2 
Remove Jumper J29 on upper circuit board (zone 1) – Note there must be no 
trigger input at terminal J33 (Link1). 
Step 3 
Connect two cables between circuit board 1 and circuit board 2: 
Cable 1: Board 1 Master Connection OUT  Master Connection IN Board 2 
Cable 2: Board 2 Master Connection OUT  Master Connection IN Board 1 
Example for AOV20-10 with zone one as a master. Once step 3 is completed: 
Upper board: 
J15, J16, J19, J24 
Lower Board: 
J17, J24. 










