User Manual

18
©2014. CyberPower Systems, Inc. All rights reserved.
16.
Download progress window will open after click Send button
17.
After upload binary file Hyperterminal will show as below
You can check to see if the firmware upgrade is successful by checking the
“CyberPower System Firmware Version” after login.
Note :
1.
Please do not turn the ATS off and ensure the quality of selected source
when
processing firmware upgrade. Source will not perform switch function
when upgrading firmware.
2. Press “3” to exit the main menu of firmware upgrade.
RMCARD
There are two files to update in order to upgrade the firmware:
- cpssnmpfw_XXX.bin
- cpssnmpdata_XXX.bin
Note that the XXX is not part of the file name but is where the version number
in the filename is given.
Use the following steps to upgrade the firmware.
1.
Download the latest firmware from cpsww.com
2.
Extract the file to “C:\”
3.
Open a command prompt window and navigate to “C:\”
4.
Login to the Remote Management Card with FTP command, type
-
ftp (after entering ftp mode, ftp> will display in the command prompt as
shown below instead of C:\ )
-
ftp> open
-
To [current IP of the RMCARD] [port] (for example: To 192.168.22.126 21
[21 is the default ftp port for the RMCARD])
-
Input USER NAME and PASSWORD (same as the administrator account in
Web interface default: cyber ; cyber)
5.
Upload the cpssnmpfw_XXX.bin, type
-
ftp > bin
-
ftp > put cpssnmpfw _XXX.bin
6
.
Upgrade complete, type
-
ftp > quit
Operation