User Manual

7
©2014. CyberPower Systems, Inc. All rights reserved.
Installation Guide
For 1U Series
Step 1. Mounting Bracket Installation
Use provided Mounting Bracket Screws (16) to attach Mounting
Brackets (2) to the ATS.
Step 2. ATS Mounting
Use supplied Washers (4) and Screws (4) to secure the ATS to your
existing rack system.
Step 3: Cord Retention Tray Installation (optional)
Attach Cord Retention Tray to the ATS with 4 supplied Cord
Retention Tray Mounting Screws.
Use provided Cable Ties to fasten each cord to the Cord
Retention Tray.
Technical Specifications
Switched Series Metered Series
Model Name PDU30SWT17ATNET PDU30SWHVT19ATNET PDU30MT17AT PDU30MHVT19AT
Input
Nominal Voltage 100-120V 200-240V 100-120V 200-240V
Frequency 50/60Hz
Derated Input Current 24A
Plug Type (2) NEMA L5-30P (2) NEMA L6-30P (2) NEMA L5-30P (2) NEMA L6-30P
Power Cord Type SR (10 AWG)
Power Cord Length 10 ft/3.05 m
Output
Nominal Voltage 100-120V 200-240V 100-120V 200-240V
Derated Output Current
5-20R: 16A
L5-30R: 24A
C13: 12A
C19: 16A
L6-30R: 24A
5-20R: 16A
L5-30R: 24A
C13: 12A
C19: 16A
L6-30R: 24A
Derated Output Current
(each bank)
20A
Bank Number 2
Outlet Type
(16) NEMA 5-20R
(1) NEMA L5-30R
(16) IEC C13
(2) IEC C19
(1) NEMA L6-30R
(16) NEMA 5-20R
(1) NEMA L5-30R
(16) IEC C13
(2) IEC C19
(1) NEMA L6-30R
Outlet Number 17 19 17 19
Circuit Breaker Yes
Transfer Time
Typical: 8-12ms
16ms max @ 60Hz/ 18ms max @ 50Hz
Management and Communications
Multifunction LCD Readout Voltage, Frequency, Load, Current, HW/FW Version, Network Information
Software PowerPanel® Business Edition
SNMP/ HTTP Capable Yes, with RMCARD203
Yes, with optional
RMCARD202/203
Connectivity RJ45 (Serial Port)
Sensor Capable Optional
Physical
Dimension (W x H x D) 17.05" x 3.5" x 9.3"/433mm x 88mm x 236mm
Environmental
Humidity 0 to 95% Non-condensing
Altitude 13100 ft/4000 m
Temperature 32
o
F to 113
o
F/0
o
C to 45
o
C
Safety Approvals
Certifications UL 60950-1, FCC Class A
* All specifications are subject to change without notice.
Please use only the provided screws through the entire installation process.