User’s Manual Professional Rack Mount UPS PR1500 / PR2200 ADDITIONAL INSTALLATION TIPS CAN BE FOUND AT: www.cyberpowersystems.com/support.
TABLE OF CONTENTS IMPORTANT SAFETY WARNINGS…………….……………………………………….………1 INSTALLING YOUR UPS SYSTEM…………………….………………………………………2 - UNPACKING…… ……………………………………………………………….2 - HARDWARE INSTALLATION GUIDE…………………………………………2 BASIC OPERATION……………………………………….....................................................3 - FRONT PANEL DESCRIPTION..................................................................3 - REAR PANEL DESCRIPTION…………………………………………...…….4 BATTERY REPLACEMENT AND STORAGE………………………………………….……..
PR1500/ PR2200 Guaranteed Uninterruptible Power System IMPORTANT SAFETY WARNINGS (SAVE THESE INSTRUCTIONS) This manual contains important instructions that should be followed during installation and maintenance of the UPS and batteries. Please read and follow all instructions carefully during installation and operation of the unit. Read this manual thoroughly before attempting to unpack, install, or operate.
INSTALLING YOUR UPS SYSTEM UNPACKING Inspect the UPS upon receipt. The box should contain the following: (1) UPS Unit; (1) User’s Manual for UPS; (2) Rack mount Brackets; (2) Stands; (1) Telephone Cable (1) PowerPanel PlusTM Software Disk; (1) User’s Manual for PowerPanel PlusTM; (1) PowerPanelTM Software Disk; (1) User’s Manual for PowerPanelTM; (2) Serial Interface Cable (DB-9); (1) Serial-to-USB cable; (1) Warranty Registration Card. HARDWARE INSTALLATION GUIDE 1.
PR1500/ PR2200 Guaranteed Uninterruptible Power System 9. To maintain optimal battery charge, leave the UPS plugged into an AC outlet at all times. 10. To store your UPS for an extended period, cover it and store with the battery fully charged. Recharge the battery every three months to insure battery life. BASIC OPERATION FRONT PANEL DESCRIPTION Power Switch Press the power button to turn the UPS ON or OFF Test Switch Professional Rack Mount UPS performs a self-test automatically. When powered on.
Battery Indicators This indicator shows a visual indication of the battery charge. If battery capacity is under 20%, no indicator LED will illuminate and UPS starts beeping. Load Level Indicators This indicator shows a visual induction of the UPS load. The load indicator LED will turn orange if the load is between 80 and 100%. If the load is under 20%, no indicator LED will illuminate.
PR1500/ PR2200 Guaranteed Uninterruptible Power System Communication Protection Ports (RJ11/RJ45) Ports protect standard modem, fax, telephone line or network cable. Dual Serial Ports Professional Rack Mount UPS provides two serial ports to allow connection and communication between the UPS and two computers. This allows the simultaneous shutdown of two computer systems.
BATTERY REPLACEMENT Contact your dealer or call the number in this manual for information on battery replacement. The order numbers for the battery are BA-PR1500 for PR1500; BA-PR2200 for PR2200 Read and follow the IMPORTANT SAFETY INSTRUCTIONS before servicing the battery. Service the battery under the supervision of personnel knowledgeable of batteries and their precautions. Servicing the battery can only be performed by trained personnel. CAUTION! Use only the specified type of battery.
PR1500/ PR2200 Guaranteed Uninterruptible Power System 4. Remove the four retaining screws. 3. Disconnect the black and red cable. 5. Pull the battery pack out from the unit. 6. Slide a new battery pack into the unit. Assemble the screws, cover, cable and front panel in the reverse sequence of above steps. 7.
DEFINITIONS FOR LED INDICATORS Using Circuit Power Wiring On On Fault Off On AVR Condition Alarm Battery Breaker Off Off Set Off Off Flash Off Set Off ON Off On Off Set Off Off On/Off Off On Set Two Beeps Off On/Off Off On Set Rapid Beeps Set Long Beep On/Off On/Off On/ Off /Flash On/Off Off Off Off On Up Long Beep On On/Off On/ Off /Flash Off Set None Off Off Off Off Set Off On/Off On On/ Off /Flash On/Off Set/Up None 8 1 Normal AVR- Max.
PR1500/ PR2200 Guaranteed Uninterruptible Power System TROUBLESHOOTING Problem Outlets do not provide power to equipment Possible Cause Solution Circuit breaker is tripped due to overload. Turn the UPS off and unplug at least one piece of equipment. Wait 10 seconds, reset the circuit breaker and then turn the UPS on. Batteries are discharged. Recharge the unit for at least 4 hours Unit has been damaged by a surge or spike. The UPS does not perform expected runtime. The UPS will not turn on.
TECHNICAL SPECIFICATIONS Model Capacity Capacity (VA) (Watts) PR1500 PR2200 1500VA 1000W 2200VA 1500W Input Voltage Range Frequency Range Output On Battery Output Voltage 85 -150Vac 47 - 63Hz Pure Sine Wave at 120Vac +/- 5% On Battery Output Frequency Transfer Time (Typical) Overload Protection 60Hz +/- 1% 4ms On Utility: Circuit Breaker, On Battery: Internal Current Limiting Surge Protection and Filtering Lightning / Surge Protection Internet Ready (DSL / Phone / FAX / Modem Protection) Physical
PR1500/ PR2200 Guaranteed Uninterruptible Power System LIMITED WARRANTY AND POWER CONTROL GUARANTEE In purchasing a PR1500 / PR2200 in the United States or Canada, the original end user receives a Limited Warranty and CyberPower's Power Control Guarantee from Cyber Power Systems (USA), Inc. (for ease of reading, referred to as "CyberPower"). The Limited Warranty and the Power Control Guarantee are intended to be the original end-user's exclusive rights and remedies.
To be covered you must still be the owner of the Product at the time of the failure that results in the claim made under this Limited Warranty. Exclusive Remedies Under Limited Warranty.
PR1500/ PR2200 Guaranteed Uninterruptible Power System In the event of damage to the Connected Equipment, your exclusive remedy, and CyberPower's sole obligations are as follows for Connected Equipment.
1. The fair market value of the Connected Equipment as established by the lower of (a) the average price the same or similar items are being sold for on E-bay, (b) the price list of Orion Blue Book on the date of occurrence (or if such price list is no longer published, a published or announced price list reasonably selected by CyberPower), or (c) the lowest price the same or similar items can be purchased for in the United States. 2.
PR1500/ PR2200 Guaranteed Uninterruptible Power System CyberPower Does Not Cover or Undertake Any Liability in Any Event for Any of the Following: 1. Loss of or damage to data, records, or software or the restoration of data or records, or the reinstallation of software. 2.
FCC Notice This equipment has been tested and found to comply with the limits for a Class B Digital Device, pursuant to Part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference in residential installation. This equipment generates, uses and can radiate radio frequency energy and, if not installed and used in accordance with the instructions, may cause harmful interference to radio communications.