User`s manual

CyberPower Remote Management System
11
[UPS->Configuration] Configure the parameters of the UPS.
Item Definition
Supplied Power
Voltage
Set the output voltage which is supplied to
the connected equipment.
Utility Power Failure Condition
High/Low Input (or Output)
Voltage Threshold
When the utility power voltage or output
voltage (according to the UPS support) is
higher/lower than the threshold, the UPS will
supply battery power to the connected
equipment. This setting only comes into
effect after a restart of the UPS.
Frequency Tolerance
Sets the acceptable range of the input
frequency. It will be in power failure condition
if out of this tolerance.
Operation
Normal Normal working mode of the UPS.
Generator Mode
If the UPS uses generator as its input power,
this option should enable the UPS to function
normally. If this option is selected, the UPS
will be forbidden to enter Bypass mode or
ECO mode to protect the powered
equipment.
ECO Mode
On-line UPS enters Economy mode. The
UPS will enter Bypass mode when the input
voltage/frequency is in the range of
thresholds. Once the utility
voltage/frequency exceeds thresholds, the
UPS will supply power to its load.
Manual Bypass
Determine whether to allow the UPS to enter
Manual Bypass mode. If this option is
selected, the UPS will be forced to enter
Bypass mode.
Bypass
Qualify Bypass
No Bypass: If this option is selected, the
UPS will not enter Bypass mode and will
stop supplying output power.
Check Volt/Freq: If the utility voltage is in
range of the voltage thresholds and the utility
frequency is in range of the frequency
tolerance, the UPS will enter Bypass mode.