[UPS->Master Switch] Switch the output power of the UPS to be on or off.
Item Definition
Reboot UPS Turn the UPS off and back on
Turn UPS Off Turn the UPS off.
UPS Sleep
This command is available under Utility Power
Failure Mode. It will make UPS under sleep mode
until power is restored.
Cancel Switch Cancel a pending action to turn the UPS off.
Turn UPS On Turn the UPS on.
Shutdown/Sleep Delay
How long the UPS waits before it turns off in
response to a "Reboot UPS", "Turn UPS off" or "UPS
Sleep" command.
Reboot Duration
After the UPS is turned off, Reboot Duration defines
how long the UPS waits before it turns on in
response to "Reboot UPS" command.
Signal Clients to Shutdown
Select this option to notify PowerPanel Business
Edition Clients before UPS turning off.
The Shutdown Delay for the UPS can be modified to
ensure a graceful shutdown.
[UPS->Bank Control] Display the current status of each Bank. Also, it provides on/off control for
the Non-Critical Outlet Bank. Outlet Index and Device Name display the device that is powered
by the specific bank.
Item Definition
Non-Critical Turn the non-critical bank on/off immediately.
Outlet Index The index of outlet.
Device Name Device Name on this outlet.
[UPS->Diagnostics] When a power failure occurs, the UPS will supply battery power to all
connected equipment immediately. The UPS must have sufficient runtime for all connected
computers to be shut down properly.
The UPS/Diagnostics page provides the information to verify if the UPS has sufficient battery
runtime for the connected computers to shutdown properly. Perform a complete runtime
calibration to ensure an accurate estimate of the runtime for the connected load.
Battery Test
The Battery Test will force the UPS to switch to battery power for 10 seconds. This allows the