Recharged Capacity
When the utility power restores, the UPS will
start to recharge after the specified battery
capacity is met.
Returned Delay
When the utility power restores, the UPS will
delay the restoration of output power. This
option can be used to stagger the startup
time of multiple UPSs to avoid overloading
the utility power circuit or power source. The
Returned Delay will take effect every time
when the UPS restores power. This also
includes the scheduling and user controlling
task.
Battery
Low Battery Threshold
When the UPS supplies battery power and
the remaining capacity is lower than this
threshold, the UPS will alarm.
External Battery Pack
Set the amount of external battery packs.
This allows for an accurate runtime
estimation based upon the total number of
batteries.
System
Cold Start
Set the ability of the UPS can start in the
absence of input power. When this option is
enabled the UPS can be turned on without
having input power.
Audible Alarm
If this option is enabled, the UPS will issue
an audible alarm when supplying battery
power or output overload.
Non-Critical Outlet Bank
Turn Off Threshold
When supplying battery power, the UPS will
power off the NCL outlet if the remaining
battery capacity is lower than this threshold.
Turn off Delay Time
When supplying battery power, the UPS will
power off this NCL outlet after this delay time
is met.
Turn On Delay Time
When the utility power restores, the UPS will
restore the output of the NCL outlet after the
delay time is met. This prevents excessive
power consumption caused by all the
connected equipment rebooting at the same
time.