User`s manual
CyberPower Remote Management System
12
[UPS->Master Switch] Switches the output power of the UPS to be on or off.
Items Definition
Reboot UPS Turn the UPS off and back on
Turn UPS Off Turn the UPS off.
UPS Sleep
This command is available under Utility Power
Failure Mode. It can make UPS under sleep mode
until power restores.*
Cancel Switch Cancel a pending action to turn the UPS off.
Turn UPS On Turn the UPS on.
Shutdown/Sleep Delay
How long the UPS waits before it turns off in
response to a "Reboot UPS", "Turn UPS off" or "UPS
Sleep" command.
Reboot Duration
After the UPS is turned off, Reboot Duration defines
how long the UPS waits before it turns on in
response to "Reboot UPS" command.
Signal Clients to Shutdown
Select this option to notify PowerPanel Business
Edition Clients before UPS turning off.
The Shutdown Delay for the UPS can be revised to
ensure a graceful shutdown.
*Some UPS may not support this command
[UPS->Bank Control] Displays the current status of each Bank. Also, it provides on/off control
for the Non-Critical Outlet Bank, Outlet index and Device Name displays the device name
provided power by the specific outlet.
Non-Critical Turn the non-critical bank on/off immediately
Outlet Index The index of outlet
Device Name Device Name on this outlet
[UPS->Diagnostics] When a power failure occurs, the UPS will supply battery power to all
connected equipment immediately. The UPS must have sufficient runtime for all connected
computers to be shut down properly.
The UPS/Diagnostics page provides the information to verify if the UPS has sufficient battery
runtime for the connected computers to shutdown properly. Perform a complete runtime
calibration to ensure and accurate estimate of the runtime for the connected load.
Battery Test
The Battery Test performs a battery test to verify the battery conditions and provides information