User Manual

CyberPower Remote Management System
33
bypasshvlimit
10 | 15
Set high bypass voltage in percentage. If the utility
voltage exceeds thresholds, the UPS will be forbidden to
enter Bypass mode.
bypasslvlimit
10 | 15 | 20
Set low bypass voltage in percentage. If the utility
voltage exceeds thresholds, the UPS will be forbidden to
enter Bypass mode.
rechargedelay
0 | 60 | 120 | 180 | 300 | 600 |
1200 | 1800 | 3600
Set the recharge delay in seconds. When the utility
power restores, the UPS will start to recharge until the
specified delay is expired before restoring output power.
rechargecap
0 | 15 | 30 | 45 | 60 | 75 | 90
Set the recharge capacity in percentage. When the
utility power restores, the UPS will start to recharge until
the specified battery capacity is met before restoring
output power.
workmode
normal | eco10% | eco15% |
generator | bypass
normalNormal working mode of the UPS.
eco10%On-line UPS enters Economy 10% mode.
eco15%On-line UPS enters Economy 15% mode.
generatorIf the UPS uses generator as its input
power, this option should enable the UPS to function
normally. If this option is selected, the UPS will be
forbidden to enter Bypass mode to protect the powered
equipment.
bypassDetermines whether to allow the UPS to enter
Manual Bypass mode. If this option is enabled, the UPS
will be forced to enter Bypass mode.
returndelay
0 ~ 600
When the utility power restores, the UPS will start to
recharge until the specified delay is expired before
restoring output power. The numbers in the range 1 to
600 seconds are numbers divisible by 5.
Example 1:
To view the available value voltage this UPS output power can be set.
CyberPower > upscfg supply?
100
110
115
Example 2:
To define bypass condition as check utility voltage only
CyberPower > upscfg bypasscond voltonly