Firmware Upgrade
By upgrading the firmware, you can obtain both the new features and updates/improvements to existing
functionality. You can check the “Firmware version” on the [System->About] page on the web user
interface. There are two files to update in order to upgrade the firmware version.
- A. cpsrm2scfw_XXX.bin
- B. cpsrm2scdata_XXX.bin
Note: Please do not turn the UPS off when processing the Firmware upgrade.
Method 1: Using FTP command
Use the following steps to upgrade the firmware:
1. Download the latest firmware
2. Extract the downloaded files to “C:\”
3. Open a command prompt window
4. Login to the CyberPower Remote Management Card with FTP command, in the command prompt
type:
(1) ftp
(2) ftp > open
(3) To [current IP address of RMCARD] [port]; EX: To 192.168.22.126 21
(4) Input USER NAME and PASSWORD (same as the administrator account in web user interface,
see page 6 for default factory settings)
5. Upload file A, type:
ftp > bin
ftp > put cpsrm2scfw_XXX.bin
6. Upload is now complete, type:
ftp > quit
7. The system will reboot after you type “quit”
8. Login to the FTP again as step 4
9. Upload file B, type:
ftp > bin
ftp > put cpsrm2scdata_XXX.bin
10. Upload is now complete, type:
ftp > quit
11. The system will reboot after you type “quit”