User’s Manual Professional Rack Mount LCD Series PR1000ELCDRT2U/PR1500ELCDRT2U/ PR2200ELCDRT2U/ PR3000ELCDRT2U K01-0000145-01
IMPORTANT INSTRUCTIONS IMPORTANTSAFETY SAFETY INSTRUCTIONS This manual contains important instructions. Please read and follow all instructions carefully during installation and operation of the unit. Read this manual thoroughly before attempting to unpack, install, or operate the UPS. CAUTION! The UPS must be connected to a grounded AC power outlet with fuse or circuit breaker protection. DO NOT plug the UPS into an outlet that is not grounded.
INSTALLING YOUR UPS SYSTEM UNPACKING The box should contain the following: ® (1) UPS unit x 1; (2) User manual x 1; (3) Phone line x 1; (4) PowerPanel Business Edition software CD x 1; (5) USB A+B type cable x 1; (6) Rack mount Brackets x 2; (7) Emergency Power Off Cable (gray) x 1; (8) Serial Interface Cable (DB-9) x 1; (9) Power cord x 5 AUTOMATIC VOLTAGE REGULATOR(AVR) The PR1000ELCDRT2U/RE1500LCDRT2U/RE2200LCDRT2U can stabiliz the consistent utility power.
INSTALLING YOUR UPS SYSTEM (continued) 5. Press the power switch to turn the UPS on. The Power-On indicator light will illuminate. If an overload is detected, an audible alarm will sound and the UPS will emit one long beep. In order to reset it, turn the unit off and unplug some equipment from outlets. Make sure your equipment carry a load current within the unit’s safe range, (refer to the technical specifications), and then turn the unit on. 6. Your UPS is equipped with an auto-charge feature.
BASIC OPERATION (continued) 7 PR1000ELCDRT2U 8 9 13 14 PR1500ELCDRT2U 250V,10A LOAD CRITICAL LOAD 250V,10A 5 250V,10A 6 11 12 10 7 13 9 8 14 6 PR2200ELCDRT2U PR3000ELCDRT2U Expansion Port Provides SNMP Card Communication AC INPUT EPO 5 15 16 Serial Port I (PRIMARY) Serial Port II 11 12 IN OUT 10 5. Battery Backup, Surge Protected and AVR protected Outlets This unit provides a total of six outlets with battery backup and surge protection.
BATTERY REPLACEMENT Read and follow the IMPORTANT SAFETY INSTRUCTIONS before servicing the batteries: Servicing the batteries should only be performed by professionals. Please Contact your dealer, or email to: service@cyberpower-eu.com. Make a note for the replacement battery pack number, (RBP832), regarding PR1000ELCDRT2U and PR1500ELCDRT2U models; (RBP842), regarding PR2200ELCDRT2U model. CAUTION! Use only the specified type of battery: BP7-12 for PR1000ELCDRT2U/PR1500ELCDRT2U, HR9-12 for PR2200ELCDRT2U.
BATTERY REPLACEMEN (continued) BATTERY REPLACMENT PROCEDURE: 1. Remove the front panel on the right side. 2. Remove the two retaining screws of the cable protection cover then remove the cover. 3. Remove the two retaining screws of the cable connectors. 4. Disconnect the black wire and red wire from the battery. 6. Put the new battery packs back into the compartment. Tighten up the screws and replace the cable protection cover and the front panel.
DEFINITION FOR ILLUMINATED LCD INDICATORS 1. Input voltage meter: This meter measures the AC voltage from the wall outlet. The INPUT voltage readout is used to identify the input voltage information. This can be used as a diagnostic tool to identify poor-quality input power. Units are listed in V (Volts). When the UPS connect to any equipment, the AVR can provide a stable 220/230/240V power output.
LCD SETUP FUCTIONS 1. General Mode: a. Press the “Display-Toggle” button to check the status of the UPS status: 1 2 3 4 5 6 7 8 9 Item Input Voltage Output Voltage Output Frequency Load Estimate Run Time Load Capacity Battery Capacity Centigrade Fahrenheit Unit V V Hz Kw Min % % ℃ ℉ b. Press and hold the “Display-Toggle” button for 4 seconds, If the machine is in the Battery Mode with active alarm, it will become silent. If the machine is in the Line Mode, a self- diagnostic test will take place. c.
LCD SETUP FUCTIONS Step 4: To save the value and return to general mode, press and hold the toggle for 4 seconds. Note! If the UPS is left idle for over 30 seconds during setup, it will turn off the backlight and return to general mode automatically. Note! If the user does not want to save the new settings and return to the general mode, there are two methods: (1) Wait for the backlight to turn off, or, (2) By pressing and holding the “Display-toggle” key for 10 second.
TECHNICAL SPECIFICATIONS Model PR1000ELCDRT2U PR1500ELCDRT2U PR2200ELCDRT2U PR3000ELCDRT2U Capacity (VA) 1000 1500 2200 3000 Capacity (Watts) 700 1000 1600 2250 Input Input connections IEC 320 C14 IEC 320 C20 Nominal Input 220Vac – 240Vac Voltage Input Voltage Range 160Vac – 290Vac Input Frequency 50/60Hz +/- 3Hz (Auto Sensing) Range Output On Battery Output 240Vac +/- 5% Voltage On Battery Output 50/60Hz +/- 0.
TROUBLE SHOOTING Problem Possible Cause Circuit breaker has tripped due to an overload. Outlet does not provide power to equipment The UPS does not perform expected runtime. The UPS will not turn on. Batteries are discharged Unit has been damaged by a surge or spike. Uncritical outlets have turned off automatically due to an overload. Batteries are not fully charged. Batteries are degraded The on/off switch is designed to prevent damage by rapidly turning it off and on.